Sprinkler Protection for Cloud Ceilings – Phase 2: Small Area Clouds Final Report Prepared by: Dr. Jason Floyd Steve Strege Matt Benfer Hughes Associates, Inc. Baltimore, MD © August 2014 Fire Protection Research Foundation THE FIRE PROTECTION RESEARCH FOUNDATION ONE BATTERYMARCH PARK QUINCY, MASSACHUSETTS, U.S.A. 02169-7471 E-MAIL: [email protected] WEB: www.nfpa.org/Foundation —— Page ii —— FOREWORD Cloud ceilings are ceiling panels that sit beneath the structural ceiling of a room or space and are seen increasingly in commercial and industrial buildings. “Cloud” panels range in area from discrete ceiling panels with large spaces in between, to close-to-full-room-area contiguous coverage with small gaps at the perimeter wall location. NFPA 13, Standard for the Installation of Sprinkler Systems, does not have definitive guidance on automatic sprinkler installation requirements for these ceilings and in some conditions requires sprinklers at both the structural ceiling and cloud ceiling panel elevations. Recent NFPA 13 change proposals were rejected based on a lack of validation of modeling results. The Fire Protection Research Foundation initiated this project to obtain an understanding of how cloud ceiling panels impact sprinkler actuation thresholds with an overall goal to provide the technical basis for sprinkler installation requirements. A Phase 1 study investigated the effectiveness of sprinklers on large area clouds. Phase 2 of this work, which is covered in this report, focused on developing guidance for sprinkler installation requirements for small area clouds by determining the maximum gap size between the wall and cloud edge at which ceiling sprinklers are not effective. The Research Foundation expresses gratitude to the report authors Dr. Jason Floyd, Steve Strege, and Matt Benfer, who are with Hughes Associates, Inc. located in Baltimore, MD. The Research Foundation appreciates the guidance provided by the Project Technical Panelists, the funding provided by the project sponsors, and all others that contributed to this research effort. The content, opinions and conclusions contained in this report are solely those of the authors. About the Fire Protection Research Foundation The Fire Protection Research Foundation plans, manages, and communicates research on a broad range of fire safety issues in collaboration with scientists and laboratories around the world. The Foundation is an affiliate of NFPA. About the National Fire Protection Association (NFPA) NFPA is a worldwide leader in fire, electrical, building, and life safety. The mission of the international nonprofit organization founded in 1896 is to reduce the worldwide burden of fire and other hazards on the quality of life by providing and advocating consensus codes and standards, research, training, and education. NFPA develops more than 300 codes and standards to minimize the possibility and effects of fire and other hazards. All NFPA codes and standards can be viewed at no cost at www.nfpa.org/freeaccess. Keywords: automatic sprinkler systems, cloud ceilings, automatic sprinkler installation —— Page iii —— —— Page iv —— PROJECT TECHNICAL PANEL Jarrod Alston, Arup Melissa Avila, Tyco Fire Protection Products Bob Caputo, Fire and Life Safety America Dave Fuller, FM Global Dave Lowrey, City of Boulder Fire Rescue Jamie Lord, ATF Fire Research Laboratory Steven Scandaliato, SDG LLC Karl Wiegand, Global Fire Sprinkler Corporation Matt Klaus, NFPA Staff Liaison PROJECT SPONSORS American Fire Sprinkler Association National Fire Sprinkler Association The Reliable Automatic Sprinkler Company Viking Corporation —— Page v —— —— Page vi —— Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds Prepared for Amanda Kimball National Fire Protection Research Foundation 1 Batterymarch Park Quincy, MA 02169 Prepared by Dr. Jason Floyd Steve Strege Matt Benfer Hughes Associates, Inc. 3610 Commerce Dr., Suite 817 Baltimore, MD 21227 July 31, 2014 FIRE SCIENCE & ENGINEERING Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE ii TABLE OF CONTENTS BACKGROUND ............................................................................................................................. 1 TASK 1: EXPERIMENTAL PROGRAM AND RESULTS ............................................................... 2 2.1. Experimental Setup ...................................................................................................... 2 2.1.1. Cloud Array ......................................................................................................... 2 2.1.2. Instrumentation ................................................................................................... 3 2.1.3. Test Matrix .......................................................................................................... 4 2.2. Experimental Procedure............................................................................................... 4 2.3. Experimental Results ................................................................................................... 5 2.4. FDS Modeling of Experiments ..................................................................................... 7 2.4.1. Grid Study ........................................................................................................... 8 2.4.2. Results of Experimental Simulations ................................................................... 9 2.5. Task 1 Summary ......................................................................................................... 11 3. TASK 2: NUMERICAL MODELING OF CLOUD CEILING CONFIGURATIONS.......................... 11 3.1. Methodology ............................................................................................................... 11 3.1.1. FDS Model ........................................................................................................ 11 3.1.2. Performance Criteria ......................................................................................... 14 3.1.3. Analysis Approach ............................................................................................ 15 3.2. Results and Analysis .................................................................................................. 18 3.2.1. First Pass Results ............................................................................................. 18 3.2.2. Second Pass Results ........................................................................................ 19 3.2.3. Third Pass Results ............................................................................................ 20 3.2.4. Fourth Pass Results .......................................................................................... 20 3.2.5. Summary of Simulations and Development of Installation Guidance ................. 20 4. SUMMARY ................................................................................................................................... 24 4.1. Summary of Task 1 and Task 2.................................................................................. 24 4.2. Limitations of Study ................................................................................................... 25 5. REFERENCES ............................................................................................................................. 25 APPENDIX A – Experimental Average Temperature Data ............................................................... 27 APPENDIX B – Operated Sprinkler Heads for FDS Simulations ..................................................... 39 B1 – Corner Fires ............................................................................................................................... 39 B1.1 8 ft Ceiling Height .......................................................................................................... 39 B1.2 14 ft Ceiling Height ........................................................................................................ 45 B1.3 20 ft Ceiling Height ........................................................................................................ 54 B2 – Cross Fires ................................................................................................................................ 59 B2.1 8 ft Ceiling Height .......................................................................................................... 59 B2.2 14 ft Ceiling Height ........................................................................................................ 60 1. 2. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 1 BACKGROUND 1. Cloud ceilings are increasingly seen in commercial and industrial facilities. The ceilings consist of ceiling panels separated by gaps that are suspended beneath the structural ceiling. Designs for cloud ceilings can vary greatly in terms of the shape and size of the panels, the gaps between panels, and the spacing between the panels and the structural ceiling. The use of cloud ceilings presents challenges for sprinkler protection that are not definitively addressed in NFPA 13. These challenges result from 1) heat from the fire plume entering the gaps between the panels and rising to the structural ceiling which may prevent sprinklers below the clouds from activating and 2) that sprinklers above the clouds may have their spray distribution blocked by the clouds. As a result, in some conditions the code would require sprinklers both below the clouds and at the structural ceiling. A prior study [1] investigated the effectiveness of sprinklers on large area clouds. A large area cloud was defined as a cloud whose extents were large enough to require at least one sprinkler per cloud. A combination of full scale testing and CFD fire modeling was used to examine the effectiveness of sprinklers on large area clouds in order to determine conditions where only sprinklers on the undersides of clouds would be required. The study concluded that where the clouds are level and co-planar, sprinklers can be omitted on the structural ceiling if: • • The gap between a wall and any cloud is less than or equal to 1 inch of gap per foot of ceiling height, or The gap between any two adjacent clouds is less than or equal to 1 ¼ inch of gap per foot of ceiling height. The study also made a number of recommendations including the following recommendation • If clouds are small enough (or have a large enough aspect ratio) that at least one sprinkler per cloud is not required based upon the listed sprinkler spacing, then a ceiling jet might encounter additional gaps between clouds. Depending upon the gap size and cloud size, the ceiling jet may not have the strength (e.g. velocity) to jump the gap in order to reach a sprinkler. Conditions under which only below cloud sprinklers would be allowed for small area clouds are likely to be much more limited than for large area clouds. A study of similar effort to this study is recommended. This report documents efforts to address the above recommendation. Specifically this project has two tasks: 1. Selected fire dynamics modeling of cloud ceiling configurations, exploring the impact of cloud and ceiling height, plenum height, gap distances, fire growth rates, and fire locations on sprinkler actuation time and temperatures at the cloud and structural ceiling levels. Configurations of cloud ceilings will include multiple clouds with a range of gap distances between clouds as well as between clouds and walls. 2. Recommendations for appropriate sprinkler installation criteria for cloud ceilings constructed with smaller clouds based on these results. To accomplish the tasks above a two task work plan was proposed for the project and accepted by the technical panel. Task 1 of the plan is a short experimental program using the Hughes movable ceiling apparatus. The primary goal of the experimental program is to collect data on fire plume interactions with small clouds in order to develop appropriate CFD model inputs for Task 2. Task 2 of the plan is to execute a matrix of simulations for the variables in Task 1 above and use those results to develop the recommendations for Task 2 above. The remainder of this report documents Task 1 and Task 2 of the work plan. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 2. TASK 1: EXPERIMENTAL PROGRAM AND RESULTS 2.1. Experimental Setup PAGE 2 2.1.1. Cloud Array A square array of nine 2 ft x 2 ft cloud panels was constructed with the panels arranged in a 3 x 3 grid. The panels were 0.25 inch thick gypsum drywall and had a 4 in. separation between panels. The panels were connected by a frame work of 2 by 4 and 2 by 2 dimensional lumber (i.e., studs). Pairs of 2 x 4 studs were placed on end approximately 16 inches apart; sets of three clouds were then centered and screwed to the pair of studs. The three sets of three clouds were then connected by three 2 x 2 studs placed at the approximate centers of the panels, perpendicular to the 2 x 4 studs. The panels were attached to the ceiling framework using four 2 x 2 studs placed near the corners of the array. These studs provided a rigidity and stability for the cloud array. The cloud array was centered beneath a 12 ft x 12 ft layer of 0.25 inch drywall that was attached to the existing structural ceiling. The bottom surface of the clouds were 18 inches below the drywall attached to the structural ceiling. A photograph of the cloud array is shown in Figure 1. There were no walls or baffles attached to the structural ceiling; therefore, this setup is equivalent to an unconfined ceiling with no layer buildup. Figure 1 – Cloud array mounted on movable ceiling A 12 inch x 12 inch propane sand burner was used to provide the heat release rates desired for testing. The flowrate to this sand burner was controlled using an Alicat mass flow controller. A shroud was constructed for the burner to prevent ambient airflows from causing excessive lean of the fire plume. The shroud consisted of a square built from four pieces of drywall measuring 2 ft x 4 ft and placed on top of four standard bricks laid on end. The propane burner was placed on the ground and centered within the shroud. A photograph of the shroud is shown in Figure 2. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 3 Figure 2 – Burner with shroud 2.1.2. Instrumentation Eighteen thermocouples were mounted to the clouds and the moveable ceiling. The thermocouple (TC) locations are shown in Figure 3. At the centers of each cloud, type K, 0.032 diameter TCs were mounted with the beads 2 inches below both the cloud and the structural ceiling. Data was recorded at a rate of 1Hz using National Instruments cDAQ hardware and LabView software. Figure 4 shows the cloud numbers and fire locations (X’s) for referencing the data spreadsheets. 8 ft 2 ft Structural Ceiling Cloud TC (2” below both clouds and structural ceiling) Fire Location Figure 3 – Plan view of ceiling plenum HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 4 9 6 3 8 5 2 7 4 1 Figure 4 – Instrumentation numbering for data acquisition and fire locations (blue x) 2.1.3. Test Matrix Twelve tests were run as part of this test series. Each test shown in the test matrix (Table 1) was run in duplicate. Three fire locations, which are illustrated in Figure 3 and Figure 4, were used: centered below a cloud (cloud center), centered between two clouds (cloud-cloud-slot), and centered between four clouds (cloud-cloud-cross). The cloud ceiling was set to two different heights: 8 ft and 16 ft above the floor. For each test, two different fire sizes were used sequentially (see Section 3.0). Table 1 – Test Matrix 2.2. Test Configuration 1 2 3 4 5 6 Cloud Center Cloud-Cloud-Cross Cloud-Cloud-Slot Cloud Center Cloud-Cloud-Cross Cloud-Cloud-Slot Ceiling Height (m [ft]) 2.4 [8] 2.4 [8] 2.4 [8] 4.9 [16] 4.9 [16] 4.9 [16] Fire Size (kW) 50, 100 50, 100 50, 100 100, 200 100, 200 100, 200 Experimental Procedure Prior to testing, the ceiling was raised to the appropriate height. The bottom of the cloud ceiling was set to either 8 ft or 16 ft. The cloud ceiling was leveled using adjustment straps attached to the sides of the structural ceiling. The propane burner was placed in the appropriate location for the specific test. All ventilation and circulation fans in the lab were turned off to prevent air currents from causing excessive flame lean. The DAQ system was turned on for a period of 1 minute or more to ensure the system was operational and to capture background temperatures. The mass flow controller was set to a zero flow and valves for the propane system were opened. A lit handheld propane torch was positioned near the propane burner prior to ignition. The mass flow controller was set to the first output level and the burner was ignited. The burner was allowed to burn at the first level for a minimum of 5 minutes. After 5 minutes, the mass flow controller was set to the second output level for a minimum of 5 minutes. The 5 minute period ensured that the temperatures reached steady-state levels. After the second 5 minute burn, the mass flow controller was secured; data was secured after the temperatures reached near ambient conditions. Overhead exhaust ventilation fans were operated until the space above the structural ceiling was clear of combustion products. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 2.3. 1JEF00019.000 PAGE 5 Experimental Results During some of the testing, the propane flame experienced some leaning as is illustrated in Figure 5. This caused the plume to shift somewhat from the intended location; however, the leaning was intermittent and varied from test to test. Figure 5 – Photograph showing a typical plume lean The ambient temperatures were between 19 and 25 ˚C at the beginning of the tests. Table 2 lists the ambient temperatures for each test. These temperatures were average temperatures taken over all 18 thermocouples during the 60 second background data acquisition time. Table 2 – Test Matrix Test Configuration 1A 1B 2A 2B 3A 3B 4A 4B 5A 5B 6A 6B Cloud Center Cloud Center Cloud-Cloud-Cross Cloud-Cloud-Cross Cloud-Cloud-Slot Cloud-Cloud-Slot Cloud Center Cloud Center Cloud-Cloud-Cross Cloud-Cloud-Cross Cloud-Cloud-Slot Cloud-Cloud-Slot Ceiling Height (ft) 8 8 8 8 8 8 16 16 16 16 16 16 Ambient Temperature (˚C) 22 25 21 21 22 21 25 24 21 19 21 19 Steady-state average temperatures were calculated for each burner output level during each test. An interval of 200 seconds was selected from each steady state period and the temperature values were averaged across this period. An example of the steady state period selection is shown in Figure 6. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 6 Figure 6 – Example of Data Processing Methodology Average steady state temperatures for Test 1A is shown in Figure 7. Appendix A contains all the average test data. The fire location is marked with a blue “X” on each figure. In general, the tests were very repeatable. Differences in average steady state temperatures for the same cloud in the repeat tests were generally less than 5 ˚C for all clouds in tests 2, 4, 5, and 6. In test 3, the largest differences between average steady state temperatures were as high as 6 ˚C. For test 1, at the 50 kW burner output, the differences in average steady state temperatures for the same cloud were less than 5 ˚C, but the largest differences at the 100 kW burner output were up to 15 ˚C. The largest difference of 15 ˚C was located below the cloud (#7) directly located above the propane burner. The average temperatures at this location were the highest out of all of the tests at 131 ˚C (test 1A) and 156 ˚C (test 1B). For all the tests, the figures show a temperature rise over all clouds for all fire locations. However, for Tests 1 and 4 with the fire centered below a cloud, only a small rise in temperature is seen for the opposite corner cloud especially as compared to the structural ceiling cloud. Taken together these observations indicate that there is the potential to activate a sprinkler over multiple cloud gaps from the fire location, but the permissible gap size and number of gaps is not likely to be large. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 7 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 54 48 48 73 72 69 58 55 51 77 78 72 56 57 53 95 86 74 Below Cloud Below Cloud 39 31 26 51 39 29 57 44 30 77 57 39 92 58 41 131 81 53 Figure 7 – Test 1A results (x is fire location) 2.4. FDS Modeling of Experiments FDS [2-6] was used to simulate each of the 6 tests after performing a grid study. FDS comparisons were made to the average of each pair of identical tests. The procedure in the FDS Validation Guide [5] was followed in making the comparisons to determine model error and bias. The experimental error was taken by performing a propagation of error on the test data using the standard error of the two test average, the estimated error in the thermocouple measurement (expanded error of 5 % [5]), and the manufacturer reported error for the mass flow controller (50 kW – 2.3 %, 100 kW – 1.4 %, and 200 kW – 0.9 %) adjusted to temperature [5]. Comparisons were made for each fire size separately for the cloud ceiling and the moveable ceiling locations as well as for each fire size for all locations combined for each test. Two sets of comparisons were made. The first set used the experimental data as collected. The second set attempted to account for plume lean of the fire by averaging symmetric locations. The symmetric locations are shown in Figure 8 below. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 8 Figure 8 – Symmetric locations for plume lean correction (like colors) 2.4.1. Grid Study Test 1 was used for a grid study. Three meshing schemes were evaluated during the study. The first scheme was a uniform 2 inch mesh. The second scheme was a uniform 1 inch mesh extending 1 ft to the sides of the cloud array and 2/3 ft above and below the array with the remainder of the domain a uniform 2 inch mesh. The third meshing scheme replaced the finer 1 inch mesh with an 0.5 in mesh. The three meshing schemes respectively placed 2, 4, or 8 cells across the gap between clouds. Table 3 and Table 4 below shows the results of the grid study. As can be seen in the tables, for all grid sizes the errors are 17 % or less. This is the same as the 16 % error seen for ceiling jets in the FDS Validation Guide. When all the data for a test is grouped together, little difference is seen between the three meshing strategies. However, when the data is spilt into cloud and movable ceiling measurement locations, differences are apparent. Presented in this manner the uniform mesh has a higher error than the other two meshes. The 1 inch vs 0.5 inch mesh around the clouds show similar levels of error. From this it is concluded that a modeling goal should be to target 4 cells across the gap. An additional observation is that FDS is slightly under predicting the temperatures overall (the bias over all data is less than 1). Much of this is likely the plume lean being towards the open edge of the cloud array which can be seen in Test 2 and Test 5 where the outer edge clouds next to the fire have a higher temperature than the inner clouds next to the fire. When data is separated based on location, the cloud bias is less than 1 and the movable ceiling bias is greater than 1. This is a desirable outcome as under predicting the cloud temperatures will result in conservative predictions of sprinkler operation for below cloud sprinklers. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 9 Table 3 – Grid Study Results Unadjusted Data Dataset All 50 kW data All 100 kW data 50 kW Cloud 50 kW Movable 100 kW Cloud 100 kW Movable Uniform 2 inch mesh error bias 1 inch mesh around clouds error bias 0.5 in mesh around clouds error bias 0.12 0.98 0.10 1.00 0.11 0.98 0.16 0.93 0.11 0.94 0.14 0.94 0.10 0.96 0.08 0.93 0.05 0.89 0.14 1.01 0.07 1.07 0.06 1.08 0.15 0.93 0.12 0.89 0.12 0.85 0.17 0.93 0.05 1.00 0.09 1.03 Table 4 – Grid Study Results Symmetrically Averaged Data Dataset All 50 kW data All 100 kW data 50 kW Cloud 50 kW Movable 100 kW Cloud 100 kW Movable Uniform 2 inch mesh error bias 1 inch mesh around clouds error bias 0.5 in mesh around clouds error bias 0.13 0.91 0.12 0.92 0.13 0.91 0.16 0.88 0.12 0.89 0.16 0.89 0.12 0.88 0.10 0.85 0.07 0.81 0.15 0.06 0.06 1.00 0.06 1.01 0.16 0.83 0.16 0.87 0.14 0.80 0.17 0.89 0.06 0.95 0.09 0.99 2.4.2. Results of Experimental Simulations Based on the grid study, the 1 inch mesh around the clouds with a 2 inch mesh for the remainder of the domain was used as the meshing strategy in FDS to simulate all 6 tests. Figure 9 below shows scatterplots for the measured vs. the predicted data where the diagonal line represents perfect agreement. The plots show a good agreement between FDS and the measured data. The plots indicate somewhat more scatter for the movable ceiling than the cloud ceiling. The negative bias observed in the grid study for the cloud ceiling locations can also be seen in the plots (more data below the diagonal line for the clouds than above it). HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 160 PAGE 10 160 120 Cloud Data All Data 140 Movable Ceiling Data 140 100 80 60 Predicted Temperature (°C) Predicted Temperature (°C) Predicted Temperature (°C) 100 120 120 100 80 60 80 60 40 40 40 20 20 20 40 60 80 100 120 Measured Temperature (°C) 140 160 20 20 40 60 80 100 120 Measured Temperature (°C) 140 160 20 40 60 80 100 Measured Temperature (°C) 120 Figure 9 – Scatterplots of predicted vs. measured data Table 5 and Table 6 below show the results for all simulations for the unadjusted and averaged test data. With the exception of the unadjusted data for Test 2 at 100 kW, all the predictions fall within the ceiling jet error noted in the FDS Validation Guide. As with the grid study, a slight negative bias is seen for the cloud predictions and slight positive bias is seen for the movable ceiling predictions. The average biases are not large. The average cloud bias is 0.95 (under predict by 5 %), and the average movable ceiling bias is 1.02 (over predict by 2 %). Table 5 – All Test Simulation Results Unadjusted Data Test 1 2 3 4 5 6 Fire Size (kW) 50 100 50 100 50 100 100 200 100 200 100 200 All Data error bias 0.10 1.00 0.11 0.94 0.13 0.98 0.19 0.95 0.15 0.98 0.17 1.01 0.03 1.00 0.05 0.94 0.04 1.00 0.06 0.97 0.05 1.02 0.04 0.97 Cloud error bias 0.08 0.93 0.12 0.89 0.13 0.94 0.22 0.93 0.13 0.94 0.17 0.98 0.02 0.97 0.04 0.93 0.02 0.96 0.06 0.92 0.03 0.99 0.04 0.95 Movable error bias 0.07 1.07 0.05 1.00 0.13 1.02 0.17 0.97 0.16 1.03 0.18 1.04 0.01 1.02 0.05 0.96 0.04 1.04 0.02 1.01 0.04 1.05 0.04 0.99 HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 11 Table 6 – All Test Simulation Results Symmetrically Averaged Data Test 1 2 3 4 5 6 2.5. Fire Size (kW) 50 100 50 100 50 100 100 200 100 200 100 200 All Data error bias 0.10 1.00 0.11 0.94 0.10 0.97 0.12 0.93 0.14 0.98 0.17 1.01 0.03 1.00 0.05 0.94 0.04 1.00 0.05 0.96 0.05 1.02 0.04 0.97 Cloud error bias 0.08 0.93 0.12 0.89 0.04 0.93 0.03 0.89 0.12 0.94 0.17 0.98 0.02 0.97 0.04 0.93 0.00 0.96 0.02 0.92 0.03 0.99 0.04 0.95 Movable error bias 0.05 1.06 0.06 1.00 0.12 1.02 0.16 0.97 0.16 10.3 0.18 1.04 0.01 1.02 0.05 0.96 0.04 1.04 0.01 1.01 0.04 1.05 0.04 0.99 Task 1 Summary A set of six experiments using an array of nine small clouds was conducted to collect data for model development and validation. The experiments varied fire size, fire location, and ceiling height. The experimental results indicate that a portion of the energy from the fire can cross multiple cloud gaps. FDS was used to simulate all six of the experiments in two parts. The first part used Test 1 and performed a grid study. The grid study determined that four cells across the gaps results in a reasonable predictive accuracy of the below cloud and above cloud conditions. The second part used the grid determined in the first part to simulate the six tests. For all test variables it was determined that selected meshing strategy resulted in FDS predictions as accurate as the ceiling jet results in the validation guide. Additionally the bias in the predictions was appropriately conservative with the cloud ceilings slight under predicted and the structural ceiling slightly over predicted. 3. TASK 2: NUMERICAL MODELING OF CLOUD CEILING CONFIGURATIONS The goal of Task 2 was to simulate a range of cloud ceiling configurations in order to develop installation guidance and code recommendations. Simulations were performed using FDS 6.0.1. 3.1. Methodology 3.1.1. FDS Model 3.1.1.1. Geometry Modeling was based upon the geometry used in the first cloud ceiling study. This was a 30 ft by 30 ft room with an open doorway along one wall. A fixed ceiling plenum height of 2 ft was used in this study. The prior study varied plenum height; however, it determined that ceiling plenum height had little impact on the permissible cloud spacing. Geometry variables in this study were cloud size, the gap between clouds, and ceiling height. A schematic of the room geometry is shown in Figure 10. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 12 3.1.1.2. Fire The first cloud study varied fire growth and used one of five fire locations. It determined that growth rate was not a significant factor in the permissible cloud spacing; therefore, this study used a medium growth rate. The first study also determined that the gap sizes were driven by two fire locations: fire in a corner and fire directly below the intersection of four clouds. Based upon that observation, this study only used the two limiting fires hereinafter referred to as corner-fire and cross-fire. Each simulation used a medium growth fire with a 1500 kJ/m2 heat release rate based on a woodplastic mix representative of typical ordinary combustibles. This was represented as C2.13H8N4 with a 5 % soot yield and a 3.8 % CO yield that had a heat of combustion of 17 kJ/kg. Prediction of sprinkler activation time is dependent upon reasonably predicting the fire plume temperatures as a function of time. If the fire in FDS was defined as just a single burner, then until it grows in size it would be a diffuse heat source over a large area with low plume temperatures. To prevent this and keep the fire plume representative of a growing, flaming fire, the fire source in FDS was implemented as a series of concentric rectangles, see Figure 11. The fire would grow by increasing in size over one rectangle until it reached 1500 kJ/m2 and then having the next rectangle start burning. In this manner medium growth t2 fire was created that grew in size over time. Varies Cloud Panel Varies Door 9.1 m (30 ft) Figure 10 – Schematic of simulation geometry HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds Cross-fire 1JEF00019.000 PAGE 13 Corner-fire Figure 11 – Fire source implementation in FDS 3.1.1.3. Sprinklers Sprinkler activation was determined by FDS using its built-in sprinkler response model – the RTI equation. All sprinklers were modeled as quick response (RTI = 50 (m·s)1/2) with an activation temperature of 73.9 °C (165 °F). Sprinklers were positioned 5 cm (2 inches) below the clouds. Sprinklers were located at cloud centers, centered in the gap at cloud corners, and centered in the gap at the cloud edges as shown in Figure 12 (also shown for reference are the fire locations). Structural Ceiling Cloud Sprinkler Fire Location Figure 12 – Modeled sprinkler locations plus fire locations for a 3x3 cloud array HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 14 3.1.1.4. Material Properties The walls, clouds, and structural ceiling were given the properties of 3/8” gypsum wallboard. In general one would expect these surfaces to be some form of insulating (i.e. low thermal conductivity) material and gypsum is a common interior finish. The floor of the room was given the properties of 15 cm (6 in) of concrete. The floor plays little role in the overall heat balance of the room since a configuration would be considered a failure if the hot layer reached the floor prior to sprinkler activation. 3.1.2. Performance Criteria Sprinkler requirements for cloud ceilings are in NFPA 13 [7]. The purpose of NFPA 13 is “to provide to provide a reasonable degree of protection for life and property from fire through standardization of design, installation, and testing requirements for sprinkler systems, including private fire service mains, based on sound engineering principles, test data, and field experience.” The goal of this project was to determine configurations where the sprinklers would not be needed (or effective) on the structural ceiling when a cloud ceiling is present. It is obvious, and borne out by prior results, that a porous ceiling will result in increased time to sprinkler activation. Therefore, determining if a cloud configuration would require sprinklers both above and below the clouds means determining at what point the delay in activation prevents a reasonable degree of protection for life and property. Since the listing standards (e.g. UL 199 [8]) for automatic sprinklers do not contain a pre-actuation temperature requirement for the compartment gas or structure, a metric was needed to evaluate the model results. This project decided to apply a similar metric as was done for the FPRF residential sprinkler on sloped ceiling project [9]. The objective of the criteria was define a performance level that should ensure that life and property would be protected in accordance with the purpose of NFPA 13. The criteria were: 1. Below cloud sprinklers must activate due to the fire plume (e.g. ceiling jet) and not due to the development of a hot layer [9]. 2. The temperature at 1.6 m (63 in) above the floor cannot exceed 93 °C (200 °F) away from the fire and cannot exceed 54 °C (130 °F) for over two minutes [8]. 3. The temperature below either the structural ceiling or the drop ceiling cannot exceed 315 °C (600 °F) at a distance of 50 % of a standard flat ceiling sprinkler spacing [8]. 4. The backside temperature of the structural and cloud ceilings must remain below 200 °C (392 °F) [8]. Simulations were performed until one of the above criteria was met. The extent of sprinkler operation that had occurred prior to that time was then used in the development of spacing requirements. The rationale for the criteria are discussed below. 3.1.2.1. Plume vs. Layer Sprinkler Operation If the fire is able to grow large enough, at some point it will fill the plenum space above the clouds with hot gases. At that point in time the layer will drop below the clouds. Since the layer will be relatively uniform in temperature, this has the potential for near simultaneous operation of a large number of sprinklers. This condition could lead to reduced effectiveness over the sprinkler coverage area. This condition should be avoided. Rather it is desired that sprinkler operation result from the fire plume and ceiling jet where a small number of sprinklers closest to the fire operate. This is illustrated in Figure 13 below. These figures are for a simple 2x2 cloud array with a corner fire (upper left corner) and show temperature just below the clouds at the time of the first sprinkler HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 15 operation. On the left it is seen that the highest temperatures are on the cloud immediate over the fire. In this case the first sprinkler operation is the sprinkler closest to the fire, a desired outcome. On the right is the same fire with a larger gap between the clouds. At the time of the first sprinkler operation, the highest below cloud temperatures are in the opposite corner from the fire and at all the gaps between the clouds. In this case the first operation is away from the fire and results from the layer banking down below the clouds. This is an undesirable outcome. Figure 13 – Below cloud temperatures for plume (left) vs. layer activation (right), sprinkler indicated by blue circles. 3.1.2.2. Head Height Temperatures One of the goals of NFPA 13 is life safety. In the context of a fire that, in part, means ensuring conditions remain tenable for occupants to safely egress. A primary hazard to persons egressing the room with the fire is the thermal environment. In this case there is the risk of exterior burns and pulmonary injury from the inhalation of hot gasses [10]. Sprinkler operation will result in the creation of large amounts of water vapor which can condense in the lungs releasing the sensible enthalpy of the water. Keeping any extended exposure below 60 °C will greatly avoid the risk. Keeping the instantaneous exposure below 100 °C will avoid exterior skin injury. 3.1.2.3. Ceiling and Cloud Temperatures The last two criteria address hazards to the structure and other combustible materials in the room. Preventing a large area of a layer from exceeding 315 °C (600 °F), a radiative flux of < 7 kW/m2, would be expected to prevent the radiative ignition of most combustibles remote from the fire location. If this avoided, then there is a greatly reduced risk of flashover which would threaten both the structure and its occupants. Preventive high backside temperatures addresses the risk of fire spread and structural failure. Low backside temperatures reduce the risk that combustibles in contact with the backside of the ceiling will ignite. Low backside temperatures should also ensure that the structure and fasteners holding the ceiling to the structure should remain intact. 3.1.3. Analysis Approach Simulations were performed using the basic principles of spiral development. That is, an initial set of simulations was performed in a first cut attempt to bound the end result. Those simulations were analyzed, and the results used to inform the creation of the next set of simulations. The prior study determined when there is one sprinkler per cloud that a cloud-to-cloud gap spacing of 1 inch or less per foot of ceiling height would result in adequate sprinkler performance. With smaller HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 16 clouds, there is the potential for there to be clouds without sprinklers. Every gap that a ceiling jet has to cross to reach a sprinkler will result in additional heat loss from the ceiling jet into the plenum space. It was anticipated that the prior study results would not result in adequate performance. Therefore, the first modeling pass consisted of cloud ceiling heights of 8 ft, 14 ft, and 20 ft; with 3x3, 6x6, and 9x9 cloud arrays; and gap sizes of 0.5 or 1 inch per foot of ceiling height. For each simulation the time when the first criteria in Section 3.1.2 is exceeded is used to end the simulation. The sprinkler operations at that time are used to determine a permissible sprinkler spacing. The 3x3 cloud, for a 4 inch gap for an 8 foot ceiling is used below to demonstrate the analysis approach. Figure 14 shows the evaluation of the four criteria at the point in time of the first failure. In the upper left image is the backside temperature of the clouds (the fire is the white square in the upper left of the image). As can be seen there are no temperature in excess of 200 °C over the cloud area. In the upper right is the head level temperature. There are no temperatures that exceed 93 °C and while there are temperatures that exceed 54 °C; they have not done so for over 2 minutes. The bottom right image is the below cloud gas temperatures. From this it can be seen that there is no hazardous hot layer forming and that the layer has not yet dropped below the clouds as the fire plume is clearly the source of the highest temperatures. In the bottom left is the below ceiling gas temperatures. Here it can be seen that the simulation is showing a large region which exceeds 315 °C. This violates the third criteria. Figure 14 – Evaluation of Section 3.1.2 Criteria. The sprinkler operations at 240 s were then evaluated. The heads that operated were examined and the maximum and minimum radius of the region of operation was determined. The radius was measured from the center of the fire. The average radius was taken as the permissible sprinkler spacing. This is demonstrated in Figure 15 below. In the figure the average radius is 15 ft. This can be HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 17 expressed as a uniform sprinkler spacing by assuming it represents the diagonal of a square. This would yield a coverage area of 449 ft2, Figure 16. Note that this is larger than the maximum coverage area of 225 ft2 allowed in NFPA 13 for standard sprinklers. Therefore, if standard sprinklers were being used, the coverage area would have to be reduced to that given by the maximum sprinkler spacing as specified by the manufacturer. Corner Fire - 3x3 Cloud - 4 in. gap, 8 ft. ceiling at 240 seconds 30 25 Criteria 1: Criteria 2: Criteria 3: Criteria 4: Closed Heads Open Heads R(min) = 14.2 ft R(max)= 15.8 ft 15 R(max) 10 R(min) 5 0 0 5 10 15 20 25 30 Distance (feet) Figure 15 – Evaluation of Sprinkler Spacing. 21.2 ft 15 ft 21.2 ft Distance (feet) 20 288s 282s 240s 270s 449 ft2 Figure 16 – Evaluation of Sprinkler Coverage Area. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 3.2. 1JEF00019.000 PAGE 18 Results and Analysis 3.2.1. First Pass Results The first set of simulations was a pass through the permutations of 0.5 in. of gap/ft ceiling height and 1.0 in. of gap/ ft of ceiling height for 3x3, 6x6, and 9x9 clouds with ceiling heights of 8, 14, and 20 ft. All permutations were run for the corner fire location while the cross-fire location was limited to 0.5 in. of gap/ft ceiling height for the 8 ft and 14 ft ceiling heights. These are respectively shown in Table 7 and Table 8 below. Note that plots of all operated heads for all scenarios are shown in Appendix A. Table 7 – First Pass Results Corner Fire Cloud Array 3x3 6x6 9x9 Gap (in.) 4 8 7 14 10 20 4 8 7 14 10 20 4 8 7 14 10 20 Ceiling (ft) 8 14 20 8 14 20 8 14 20 Ratio (in./ft) 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 0.5 1.0 Rmin (ft) 14.2 7.2 11.4 7.6 11.4 7.8 10.4 3.9 10.5 6.2 8.2 6.4 7.2 4.1 8.7 4.4 5.6 4.5 Rmax (ft) 15.8 7.2 14.3 7.6 14.3 11.7 10.7 3.9 10.8 6.2 10.9 7.8 8.6 4.1 9.6 5.3 9.8 5.6 Coverage (ft2) 900 207 357 231 660 380 445 60.8 454 108 365 202 250 48 335 94.1 237 102 Table 8 – First Pass Results Cross Fire Cloud Array 3x3 6x6 9x9 Gap (in.) 4 7 4 7 7 Ceiling (ft) 8 14 8 14 14 Ratio (in./ft) 0.5 0.5 0.5 0.5 0.5 Rmin (ft) 7 7 7 7 7 Rmax (ft) 11.1 15.5 10.5 14.9 14.1 Coverage (ft2) 328 506 306 480 445 The following observations are noted: • The corner fire results are more limiting than the cross fire results. This echoes conclusions from the first study. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 19 • For all the cases, the 0.5 in. of gap/ft of ceiling height results in a sprinkler spacing that is larger than the 225 ft2 allowed in the code for a standard sprinkler. This indicates that the permissible gap size can be larger. • At 1.0 in. of gap/ft of ceiling height the coverage area drops significantly in most cases from >225 ft2 to 60 to 100 ft2. This indicates that a larger gap should not be used. • The coverage area decreases as the cloud size decreases. 3.2.2. Second Pass Results Since there was a significant drop in coverage area between gaps of 0.5 in./ft of ceiling height and 1.0 in./ft of ceiling height the second pass targeted gaps between those size. A gap ratio of 0.75 was used for the 8 ft ceiling. To maintain the current FDS gridding for the 14 and 20 ft ceiling heights (where the cloud grid was coarser than for the 8 ft ceiling heights) the gap ratios were 0.71 and 0.86. Results are shown in Table 9 for corner fires and in Table 10 for cross fires. Table 9 – Second Pass Results Corner Fire Cloud Array 3x3 6x6 9x9 Gap (in.) 6 10 6 10 12 6 10 12 14 Ceiling (ft) 8 14 8 14 8 14 20 Ratio (in./ft) 0.75 0.71 0.75 0.71 0.86 0.75 0.71 0.86 0.71 Rmin (ft) 7.3 7.5 5.8 7.5 6.1 5 5.2 4.9 4.4 Rmax (ft) 11.3 11.4 5.8 8.2 7.5 5.5 5.7 5.3 6.6 Coverage (ft2) 346 357 135 246 185 110 119 104 121 Table 10 – Second Pass Results Cross Fire Cloud Array 6x6 9x9 Gap (in.) 10 12 10 12 Ceiling (ft) 14 Ratio (in./ft) 0.71 0.86 0.71 0.86 Rmin (ft) 5.0 5.0 3.3 1.7 Rmax (ft) 8.7 8.3 9.3 7.15 Coverage (ft2) 396 365 346 204 The following observations are noted: • As previously seen, corner fire results are more limiting than the cross fire results. • There is an increasing drop in coverage area as the gap is increased from 0.5 in./ft of ceiling height. Gaps on the order of 0.75 in./ft of ceiling height still provide coverage areas of 100 ft2 or larger. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 20 3.2.3. Third Pass Results For the third pass the cloud arrays were increased to 12x12 and 15x15 in order to evaluate the effects of smaller clouds. Only corner fire cases were run for these simulations. Results are shown in Table 11. Table 11 – Third Pass Results Corner Fire Cloud Array 12x12 15x15 Gap (in.) 4 6 7 10 10 14 4 6 7 10 Ceiling (ft) 8 14 20 8 14 Ratio (in./ft) 0.50 0.75 0.50 0.71 0.50 0.70 0.50 0.75 0.50 0.71 Rmin (ft) 5.7 4.2 5.9 4 5.5 4.2 4.6 4.4 5.3 3.3 Rmax (ft) 7.7 5.6 7.5 4.4 8.4 5.1 6.2 4.5 6 4.1 Coverage (ft2) 180 96.0 180 70.6 193 86.5 117 79.2 128 54.8 The following observations are made: • Coverage areas have decreased from the larger cloud sizes. No 225 ft2 or larger coverage areas were seen for the 0.5 in./ft of ceiling height cloud spacing. • Coverage decreases with decreasing cloud size with the 15x15 clouds having a smaller coverage area than the 12x12 clouds. 3.2.4. Fourth Pass Results For the fourth pass two simulations were run with a 12x6 cloud array to examine the impact of having a non-square cloud. Only corner fires were run. Results are shown in Table 12. Table 12 – Fourth Pass Results Corner Fire Cloud Array 12x6 Gap (in.) 7 10 Ceiling (ft) 14 Ratio (in./ft) 0.50 0.71 Rmin (ft) 7.0 5.0 Rmax (ft) 7.8 6.0 Coverage (ft2) 219 121 It can be seen that the coverage areas for the 12x6 clouds are close to the coverage areas for the equivalent 12x12 case. This indicates that when determining how to apply spacing rules, that the smaller dimension of the cloud should be used. 3.2.5. Summary of Simulations and Development of Installation Guidance Plots of coverage area vs. gap ratio for corner fires are shown by cloud size in Figure 17. Coverage area is clearly seen to decrease with both decreasing cloud size and with increasing gap size. Figure 18 plots all ceiling heights on a single plot. In this plot there is a clear pattern that coverage area decrease with the size of the cloud array. In other words, coverage area decreases with the fraction of area that the ceiling is open. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 21 14 ft Ceiling 8 ft Ceiling 900 700 800 600 600 3x3 500 6x6 400 9x9 300 12x12 200 Coverage Area (ft2) Coverage Area (ft2) 700 15x15 500 3x3 400 6x6 300 9x9 12x12 200 15x15 100 100 0 0 0.50 0.60 0.70 0.80 Gap to Ceiling Ratio (in/ft) 0.90 1.00 0.50 0.60 0.70 0.80 Gap to Ceiling Ratio (in/ft) 0.90 1.00 20 ft Ceiling 700 Coverage Area (ft2) 600 500 400 3x3 300 6x6 9x9 200 12x12 100 0 0.50 0.60 0.70 0.80 Gap to Ceiling Ratio (in/ft) 0.90 1.00 Figure 17 – Sprinkler Coverage Area by Height, Gap Ratio, and Cloud Array for Corner Fires. 400 900 350 800 700 250 3x3 6x6 200 9x9 150 12x12 100 15x15 50 Coverage Area (ft2) Coverage Area (ft2) 300 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 0 0 0.50 0.60 0.70 0.80 Gap to Ceiling Ratio (in/ft) 0.90 1.00 0.50 0.60 0.70 0.80 Gap to Ceiling Ratio (in/ft) 0.90 1.00 Figure 18 – Sprinkler Coverage Area by Gap Ratio and Cloud Array for Corner Fires. Figure 19 below presents the same data as the prior two figures in a slightly different manner. For each cloud configuration the total area of the gaps was computed and then normalized by the total ceiling area. This results in the open area fraction of the ceiling. While the data in this figure does not show a clear pattern with the cloud array, it does indicate if the gap area fraction is less than 20 % that a 225 ft2 or larger coverage area can be used. However, immediately after crossing that threshold coverage areas for some configurations drop to 50-60 ft2. Closer examination of the reveals that the points in the lower left are primarily from the 8 ft ceiling height and that ceiling height increases towards the upper right of the point in the plot. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 400 900 350 800 700 250 3x3 6x6 200 9x9 150 12x12 100 Coverage Area (ft2) 300 Coverage Area (ft2) PAGE 22 15x15 50 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 0 0 0 0.2 0.4 0.6 Gap Area Fraction 0.8 1 0 0.2 0.4 0.6 Gap Area Fraction 0.8 1 Figure 19 – Sprinkler Coverage Area by Gap Fraction to Height Ratio and Cloud Array for Corner Fires Figure 20 and Figure 21 take the data from Figure 19 and normalizes the independent axis by the ceiling height. Figure 20 shows this data by ceiling height and Figure 21 shows all the data on one plot. For the 14 ft ceiling height, which has the most simulations, the data collapses to a clear trend. The same basic trend is seen on the other two ceiling heights. 14 ft Ceiling 900 800 800 700 700 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 Coverage Area (ft2) Coverage Area (ft2) 8 ft Ceiling 900 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 0 0 0 0.01 0.02 0.03 0.04 0.05 0.06 Gap Area Fraction to Ceiling Height (1/ft) 0.07 0 0.01 0.02 0.03 0.04 0.05 Gap Area Fraction to Ceiling Height (1/ft) 0.06 20 ft Ceiling 900 800 Coverage Area (ft2) 700 600 500 3x3 400 6x6 300 9x9 200 12x12 100 0 0 0.01 0.02 0.03 0.04 Gap Area Fraction to Ceiling Height (1/ft) 0.05 Figure 20 – Sprinkler Coverage Area by Gap Fraction to Height Ratio, Ceiling Height, and Cloud Array for Corner Fires. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 23 900 800 Coverage Area (ft2) 700 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 0 0 0.01 0.02 0.03 0.04 0.05 0.06 Gap Area Fraction to Ceiling Height (1/ft) 0.07 Figure 21 – Sprinkler Coverage Area by Gap Fraction to Height Ratio and Cloud Array for Corner Fires When all the ceiling heights are plotted together, Figure 21, there appears to be a hyperbolic section defined by the points. Figure 22 shows a best fit hyperbolic section through the data points. The function is limited to a lower bound of 36 ft2 the minimum coverage area for a standard sprinkler per NFPA 13. 900 800 Area = 0.076xRatio-2 Coverage Area (ft2) 700 600 3x3 500 6x6 400 9x9 300 12x12 200 15x15 100 0 0 0.01 0.02 0.03 0.04 0.05 0.06 Gap Area Fraction to Ceiling Height (1/ft) 0.07 Figure 22 – Figure 21 Fit with a Power Function to the Lower Edge of the Data Based on the previous figure a simple rule can be given: • The coverage area, A, is defined by the gap area fraction to ceiling height ratio, RG, according the following formula. The computed coverage area should be limited by any NFPA 13 restrictions (e.g. limited a maximum of 225 ft2 for a standard sprinkler or a manufacturer’s listed spacing for an extended coverage sprinkler). A computed coverage area less than permitted by NFPA 13 would indicate the need for sprinklers above the clouds = ܣ0.076 × ܴீ ଶ For reasons of aesthetics, it may be desirable to have a uniform array of sprinklers to match the uniform array of clouds. A sprinkler spacing rule which counts clouds may be useful. Figure 23 below plots the coverage from Figure 21 in terms of the number of clouds that could be skipped when installing HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 24 sprinklers. The figure is summarized as a tabular rule in Table 13. Note this table is applicable only far gap to ceiling height ratios of 1 in./ft or less. 4 Cloud Skipping 3 3x3 6x6 2 9x9 12x12 1 15x15 0 0 0.01 0.02 0.03 0.04 0.05 0.06 Gap Area Fraction to Ceiling Height (1/ft) 0.07 Figure 23 – Cloud Skipping by Gap Fraction to Height Ratio and Cloud Array for Corner Fires Table 13 – Sprinkler Spacing Rule Table for Cloud Skipping Cloud Size1 (ft) over 10 ft 5 ft to 10 ft 3 ft 4 in. to 5 ft 2 ft 6 in. to 3 ft 4 in. under 2 ft 6 in. Gap Area Fraction to Ceiling Height (1/ft) Every Other Every Third Each Cloud2 Cloud Cloud Up to 1 inch/ft >0.025 <0.025 >0.045 0.03≤gap≤0.045 <0.03 >0.05 0.035≤gap≤0.05 <0.035 >0.06 0.04≤gap≤0.06 <0.04 1. Dimension is gap center to gap center based on smaller cloud dimension 2. 1 inch of gap/ft of ceiling height was the limit established for large clouds in [1]. 4. SUMMARY 4.1. Summary of Task 1 and Task 2 A two-part study was conducted to determine conditions under which sprinklers could be placed only below clouds for ceilings where the cloud size is less than the listed sprinkler spacing. The first part of the study was experimental, and the second part of the study was numerical. The experimental study was conducted to develop and validate a modeling approach for cloud ceiling sprinklers using FDS. Based upon the experimental results, it was determined that at least 4 grid cells are required across a gap to resolve the appropriate partitioning of plume flow through a gap vs. plume flow across the bottom of a cloud. Modeling of all experiments using the selected gridding approach resulted in FDS predictions whose modeling uncertainty matched those for ceiling jets in the FDS validation guide. Additionally, the modeling results showed a positive bias for the structural ceiling (over predicted temperatures) and a negative bias for the cloud ceiling (under predicted temperature). This was a conservative result for the purpose of this study as it decreased the chance of a below cloud sprinkler operating. The numerical study consisted of 44 simulations. The simulations varied ceiling height, cloud size, gap size, and fire location. The simulations were done in a series of sets of simulations. The first set used HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 25 the gap size recommendation from a previous study on large area clouds and one-half that gap size. The second set refined the gap size to an intermediate value. The third set looked at smaller cloud sizes. Finally, the fourth set examined the impact of non-square (rectangular) clouds. The numerical study showed that there is a complicated relationship between cloud size, gap size, and ceiling height. This relationship was best characterized by the ratio of the gap area fraction (area of gaps over the entire area of the ceiling) to the height of the cloud ceiling. Two simple rule sets were developed. The first simply looked at coverage area as a function of the gap area fraction to height ratio. The second expressed coverage area in terms of the number of clouds that could be skipped assuming a uniform array of sprinklers. 4.2. Limitations of Study The conclusions of this study are limited to following: • Uniform gap sizes. Note that extrapolation to large gap sizes should be possible if area fractions are computed assuming all gaps are the largest size. • Uniform cloud arrays. Note that extrapolation to non-uniform arrays (tessellations of multiple cloud sizes) should be possible if area fractions are computed assuming a uniform tessellation of the smallest cloud. • Flat, level clouds all mounted at the same elevation. • Ceiling heights of 8 ft to 20 ft; however, simple scaling laws would suggest the conclusions would be applicable to larger heights. • Cloud sizes greater than 1.1 ft (The smallest cloud tested was for a 15x15 array with 10 inch gap and 20 ft cloud height). 5. REFERENCES 1. Floyd, J. and Dinaburg, J., “Sprinkler Protection for Cloud Ceilings”, Fire Protection Research Foundation, Quincy, MA, 2013. 2. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C., Overholt, K., "Fire Dynamics Simulator User's Guide," NIST SP 1019, National Institute of Standards and Technology, Gaithersburg, MD, 2013. 3. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C., Overholt, K., "Fire Dynamics Simulator Technical Reference Guide Volume 1: Mathematical Model," NIST SP 1018, National Institute of Standards and Technology, Gaithersburg, MD, 2013. 4. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C., Overholt, K., "Fire Dynamics Simulator Technical Reference Guide Volume 2: Verification," NIST SP 1018, National Institute of Standards and Technology, Gaithersburg, MD, 2013. 5. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C., Overholt, K., "Fire Dynamics Simulator Technical Reference Guide Volume 3: Validation," NIST SP 1018, National Institute of Standards and Technology, Gaithersburg, MD, 2013. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 26 6. McGrattan, K., Hostikka, S., McDermott, R., Floyd, J., Weinschenk, C., Overholt, K., "Fire Dynamics Simulator Technical Reference Guide Volume 4: Configuration Management Plan," NIST SP 1018, National Institute of Standards and Technology, Gaithersburg, MD, 2013. 7. NFPA 13 (2013), Standard for the Installation of Sprinkler Systems, National Fire Protection Association, Quincy, MA. 8. Underwriters Laboratories Inc. (1997), “Standard for Automatic Sprinklers for Fire-Protection Service,” UL-199, Northbrook, IL. 9. Floyd, J., Budnick, E., Boosinger, M., Dinaburg, J., and Boehmer, H. (2010), “Analysis of the Performance of Residential Sprinkler Systems with Sloped or Sloped and Beamed Ceilings,” The Fire Protection Research Foundation, Quincy, MA. 10. Purser, D. (2008), “Assessment of Hazards from Smoke, Toxic Gases, and Heat,” SPFE Handbook of Fire Protection Engineering, Chapter 2-6, Society of Fire Protection Engineers, Bethesda, MD. HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 27 APPENDIX A – Experimental Average Temperature Data 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 54 48 48 73 72 69 58 55 51 77 78 72 56 57 53 95 86 74 Below Cloud Below Cloud 39 31 26 51 39 29 57 44 30 77 57 39 92 58 41 131 81 53 Figure 24 – Test 1A results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 28 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 57 50 50 80 73 72 62 58 53 85 86 79 60 57 55 91 96 87 Below Cloud Below Cloud 43 33 28 56 40 33 60 45 33 86 63 42 98 62 44 156 89 59 Figure 25 – Test 1B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 29 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 51 49 49 76 74 68 64 65 52 96 98 75 70 70 54 107 107 82 Below Cloud Below Cloud 36 35 31 37 43 40 53 56 38 71 81 49 69 71 48 107 115 72 Figure 26 – Test 2A results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 30 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 50 49 49 74 75 66 63 65 51 90 93 76 67 68 52 103 103 79 Below Cloud Below Cloud 36 35 31 40 43 40 54 56 37 69 79 52 66 69 46 103 115 74 Figure 27 – Test 2B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 31 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 51 51 50 70 70 70 55 55 56 76 74 79 70 70 50 100 101 68 Below Cloud Below Cloud 31 33 30 36 39 37 42 49 39 53 63 50 69 72 49 93 101 64 Figure 28 – Test 3A results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 32 50 kW Average, SS Temperatures 100 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 49 49 49 68 71 73 53 53 56 73 73 80 68 69 50 98 102 69 Below Cloud Below Cloud 31 31 30 31 36 36 41 46 38 47 60 50 65 71 47 92 101 64 Figure 29 – Test 3B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 33 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 47 49 50 63 69 68 53 52 50 70 72 68 56 52 47 79 74 61 Below Cloud Below Cloud 42 39 38 55 52 49 51 46 40 68 61 53 62 50 42 84 69 56 Figure 30 – Test 4A results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 34 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 44 44 43 63 62 60 49 49 44 67 68 62 48 49 43 68 69 60 Below Cloud Below Cloud 40 39 36 53 52 47 49 47 38 65 64 53 53 50 40 75 73 58 Figure 31 – Test 4B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 35 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 44 48 48 60 66 64 49 50 48 67 68 64 54 51 45 76 71 57 Below Cloud Below Cloud 40 38 36 52 49 47 49 44 37 65 58 49 59 48 40 80 65 52 Figure 32 – Test 5A results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 36 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 44 44 43 64 62 60 50 50 44 69 69 62 50 50 44 69 70 60 Below Cloud Below Cloud 39 39 35 53 52 48 49 49 39 66 64 53 51 50 40 76 73 57 Figure 33 – Test 5B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 37 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 43 43 43 61 60 61 46 46 44 65 65 61 49 49 42 72 72 60 Below Cloud Below Cloud 36 36 34 49 48 45 42 42 37 58 58 50 50 49 40 72 71 55 Figure 34 – Test results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 38 100 kW Average, SS Temperatures 200 kW Average, SS Temperatures Below Structural Ceiling Below Structural Ceiling 43 43 43 59 58 59 46 46 43 63 63 59 48 49 42 69 69 57 Below Cloud Below Cloud 35 36 33 48 47 45 42 42 37 57 57 50 50 50 40 69 69 53 Figure 35 – Test 6B results (x is fire location) HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 39 APPENDIX B – Operated Sprinkler Heads for FDS Simulations B1 – Corner Fires B1.1 8 ft Ceiling Height Corner Fire - 3x3 Cloud - 4 in. gap, 8 ft. ceiling at 240 seconds 30 25 Distance (feet) 20 R(min) = 14.2 ft R(max)= 15.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 36 – 3x3 cloud, 4 in. gap, 8 ft ceiling, corner fire Corner Fire - 3x3 Cloud - 6 in. gap, 8 ft. ceiling at 235 seconds 30 25 Distance (feet) 20 R(min) = 7.3 ft R(max) = 11.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 37 – 3x3 cloud, 6 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 40 Corner Fire - 3x3 Cloud - 8 in. gap, 8 ft. ceiling at 231 seconds 30 25 Distance (feet) 20 R(min) = 7.4 ft R(max) = 7.4 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 38 – 3x3 cloud, 8 in. gap, 8 ft ceiling, corner fire Corner Fire - 6x6 Cloud - 4 in. gap, 8 ft. ceiling at 223 seconds 30 25 Distance (feet) 20 R(min) = 10.4 ft R(max) = 10.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 39 – 6x6 cloud, 4 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 41 Corner Fire - 6x6 Cloud - 6 in. gap, 8 ft. ceiling at 219 seconds 30 25 Distance (feet) 20 R(min) = 3.8 ft R(max) = 5.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 40 – 6x6 cloud, 6 in. gap, 8 ft ceiling, corner fire Corner Fire - 6x6 Cloud - 8 in. gap, 8 ft. ceiling at 213 seconds 30 25 Distance (feet) 20 R(min) = 3.9 ft R(max) = 3.9 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 41 – 6x6 cloud, 8 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 42 Corner Fire - 9x9 Cloud - 4 in. gap, 8 ft. ceiling at 215 seconds 30 25 Distance (feet) 20 R(min) = 7.2 ft R(max) = 8.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 42 – 9x9 cloud, 4 in. gap, 8 ft ceiling, corner fire Corner Fire - 9x9 Cloud - 6 in. gap, 8 ft. ceiling at 221 seconds 30 25 Distance (feet) 20 R(min) = 5.0 ft R(max) = 5.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 43 – 9x9 cloud, 6 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 43 Corner Fire - 9x9 Cloud - 8 in. gap, 8 ft. ceiling at 220 seconds 30 25 Distance (feet) 20 R(min) = 2.8 ft R(max) = 4.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 44 – 9x9 cloud, 8 in. gap, 8 ft ceiling, corner fire Corner Fire - 12x12 Cloud - 4 in. gap, 8 ft. ceiling at 228 seconds 30 25 Distance (feet) 20 R(min) = 5.7 ft R(max) = 7.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 45 – 12x12 cloud, 4 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 44 Corner Fire - 12x12 Cloud - 6 in. gap, 8 ft. ceiling at 220 seconds 30 25 Distance (feet) 20 R(min) = 5.7 ft R(max) = 7.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 46 – 12x12 cloud, 6 in. gap, 8 ft ceiling, corner fire Corner Fire - 15x15 Cloud - 4 in. gap, 8 ft. ceiling at 220 seconds 30 25 Distance (feet) 20 R(min) = 4.6 ft R(max) = 6.2 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 47 – 15x15 cloud, 4 in. gap, 8 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 45 Corner Fire - 15x15 Cloud - 6 in. gap, 8 ft. ceiling at 221 seconds 30 25 Distance (feet) 20 R(min) = 4.4 ft R(max) = 4.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 48 – 15x15 cloud, 6 in. gap, 8 ft ceiling, corner fire B1.2 14 ft Ceiling Height Corner Fire - 3x3 Cloud - 7 in. gap, 14 ft. ceiling at 253 seconds 30 25 Distance (feet) 20 R(min) = 11.4 ft R(max) = 14.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 49 – 3x3 cloud, 7 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 46 Corner Fire - 3x3 Cloud - 10 in. gap, 14 ft. ceiling at 253 seconds 30 25 Distance (feet) 20 R(min) = 7.5 ft R(max) = 7.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 50 – 3x3 cloud, 10 in. gap, 14 ft ceiling, corner fire Corner Fire - 3x3 Cloud - 14 in. gap, 14 ft. ceiling at 257 seconds 30 25 Distance (feet) 20 R(min) = 7.6 ft R(max) = 7.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 51 – 3x3 cloud, 14 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 47 Corner Fire - 6x6 Cloud - 7 in. gap, 14 ft. ceiling at 249 seconds 30 25 Distance (feet) 20 R1 = 10.5 ft R2 = 10.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 52 – 6x6 cloud, 7 in. gap, 14 ft ceiling, corner fire Corner Fire - 6x6 Cloud - 10 in. gap, 14 ft. ceiling at 254 seconds 30 25 Distance (feet) 20 R(min) = 7.5 ft R(max) = 8.2 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 53 – 6x6 cloud, 10 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 48 Corner Fire - 6x6 Cloud - 12 in. gap, 14 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 6.1 ft R(max) = 7.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 54 – 6x6 cloud, 12 in. gap, 14 ft ceiling, corner fire Corner Fire - 6x6 Cloud - 14 in. gap, 14 ft. ceiling at 250 seconds 30 25 Distance (feet) 20 R(min) = 4.2 ft R(max) = 5.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 55 – 6x6 cloud, 14 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 49 Corner Fire - 9x9 Cloud - 7 in. gap, 14 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 8.7 ft R(max) = 9.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 56 – 9x9 cloud, 7 in. gap, 14 ft ceiling, corner fire Corner Fire - 9x9 Cloud - 10 in. gap, 14 ft. ceiling at 246 seconds 30 25 Distance (feet) 20 R(min) = 5.2 ft R(max) = 5.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 57 – 9x9 cloud, 10 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 50 Corner Fire - 9x9 Cloud - 12 in. gap, 14 ft. ceiling at 245 seconds 30 25 Distance (feet) 20 R(min) = 4.9 ft R(max) = 5.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 58 – 9x9 cloud, 12 in. gap, 14 ft ceiling, corner fire Corner Fire - 9x9 Cloud - 14 in. gap, 14 ft. ceiling at 245 seconds 30 25 Distance (feet) 20 R(min) = 4.4 ft R(max) = 5.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 59 – 9x9 cloud, 14 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 51 Corner Fire - 12x12 Cloud - 7 in. gap, 14 ft. ceiling at 245 seconds 30 25 Distance (feet) 20 R(min) = 5.9 ft R(max) = 7.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 60 – 12x12 cloud, 7 in. gap, 14 ft ceiling, corner fire Corner Fire - 12x12 Cloud - 10 in. gap, 14 ft. ceiling at 238 seconds 30 25 Distance (feet) 20 R(min) = 4.0 ft R(max) = 4.4 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 61 – 12x12 cloud, 10 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 52 Corner Fire - 15x15 Cloud - 7 in. gap, 14 ft. ceiling at 238 seconds 30 25 Distance (feet) 20 R(min) = 5.3 ft R(max) = 6.0 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 62 – 15x15 cloud, 7 in. gap, 14 ft ceiling, corner fire Corner Fire - 15x15 Cloud - 10 in. gap, 14 ft. ceiling at 234 seconds 30 25 Distance (feet) 20 R(min) = 3.3 ft R(max) = 4.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 63 – 15x15 cloud, 10 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 53 Corner Fire - 12x6 Cloud - 7 in. gap, 14 ft. ceiling at 248 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 7.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 64 – 12x6 cloud, 7 in. gap, 14 ft ceiling, corner fire Corner Fire - 12x6 Cloud - 10 in. gap, 14 ft. ceiling at 240 seconds 30 25 Distance (feet) 20 R(min) = 5.0 ft R(max) = 6.0 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 65 – 12x6 cloud, 10 in. gap, 14 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 54 B1.3 20 ft Ceiling Height Corner Fire - 3x3 Cloud - 10 in. gap, 20 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 11.4 ft R(max) = 14.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 66 – 3x3 cloud, 10 in. gap, 20 ft ceiling, corner fire Corner Fire - 3x3 Cloud - 20 in. gap, 20 ft. ceiling at 267 seconds 30 25 Distance (feet) 20 R(min) = 7.8 ft R(max) = 11.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 67 – 3x3 cloud, 20 in. gap, 20 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 55 Corner Fire - 6x6 Cloud - 10 in. gap, 20 ft. ceiling at 254 seconds 30 25 Distance (feet) 20 R(min) = 8.2 ft R(max) = 10.9 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 68 – 6x6 cloud, 10 in. gap, 20 ft ceiling, corner fire Corner Fire - 6x6 Cloud - 20 in. gap, 20 ft. ceiling at 266 seconds 30 25 Distance (feet) 20 R(min) = 6.4 ft R(max) = 7.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 69 – 6x6 cloud, 20 in. gap, 20 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 56 Corner Fire - 9x9 Cloud - 10 in. gap, 20 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 5.6 ft R(max) = 9.8 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 70 – 9x9 cloud, 10 in. gap, 20 ft ceiling, corner fire Corner Fire - 9x9 Cloud - 14 in. gap, 20 ft. ceiling at 254 seconds 30 25 Distance (feet) 20 R(min) = 4.4 ft R(max) = 6.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 71 – 9x9 cloud, 14 in. gap, 20 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 57 Corner Fire - 9x9 Cloud - 20 in. gap, 20 ft. ceiling at 262 seconds 30 25 Distance (feet) 20 R(min) = 4.6 ft R(max) = 5.6 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 72 – 9x9 cloud, 20 in. gap, 20 ft ceiling, corner fire Corner Fire - 12x12 Cloud - 10 in. gap, 20 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 5.5 ft R(max) = 8.4 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 73 – 12x12 cloud, 10 in. gap, 20 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 58 Corner Fire - 12x12 Cloud - 14 in. gap, 20 ft. ceiling at 251 seconds 30 25 Distance (feet) 20 R(min) = 4.2 ft R(max) = 5.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 74 – 12x12 cloud, 14 in. gap, 20 ft ceiling, corner fire Corner Fire - 15x15 Cloud - 6 in. gap, 20 ft. ceiling at 246 seconds 30 25 Distance (feet) 20 R(min) = 8.3 ft R(max) = 8.7 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 75 – 15x15 cloud, 6 in. gap, 20 ft ceiling, corner fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 59 B2 – Cross Fires B2.1 8 ft Ceiling Height Cross Fire - 3x3 Cloud - 4 in. gap, 8 ft. ceiling at 209 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 11.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 76 – 3x3 cloud, 4 in. gap, 8 ft ceiling, cross fire Cross Fire - 6x6 Cloud - 4 in. gap, 8 ft. ceiling at 211 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 10.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 77 – 6x6 cloud, 4 in. gap, 8 ft ceiling, cross fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 60 B2.2 14 ft Ceiling Height Cross Fire - 3x3 Cloud - 7 in. gap, 14 ft. ceiling at 245 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 15.5 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 78 – 3x3 cloud, 7 in. gap, 14 ft ceiling, cross fire Cross Fire - 6x6 Cloud - 7 in. gap, 14 ft. ceiling at 246 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 14.9 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 79 – 6x6 cloud, 7 in. gap, 14 ft ceiling, cross fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 61 Cross Fire - 6x6 Cloud - 10 in. gap, 14 ft. ceiling at 247 seconds 30 25 Distance (feet) 20 R(min) = 5.0 ft R(max) = 14.9 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 80 – 6x6 cloud, 10 in. gap, 14 ft ceiling, cross fire Cross Fire - 6x6 Cloud - 12 in. gap, 14 ft. ceiling at 252 seconds 30 25 Distance (feet) 20 R(min) = 5.0 ft R(max) = 14.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 81 – 6x6 cloud, 12 in. gap, 14 ft ceiling, cross fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 62 Cross Fire - 9x9 Cloud - 7 in. gap, 14 ft. ceiling at 225 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 14.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 82 – 9x9 cloud, 7 in. gap, 14 ft ceiling, cross fire Cross Fire - 9x9 Cloud - 10 in. gap, 14 ft. ceiling at 246 seconds 30 25 Distance (feet) 20 R(min) = 3.3 ft R(max) = 15.3 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 83 – 9x9 cloud, 10 in. gap, 14 ft ceiling, cross fire HUGHES ASSOCIATES Sprinkler Protection for Cloud Ceilings, Part 2: Small Area Clouds 1JEF00019.000 PAGE 63 Cross Fire - 9x9 Cloud - 12 in. gap, 14 ft. ceiling at 242 seconds 30 25 Distance (feet) 20 R(min) = 7.0 ft R(max) = 14.1 ft 15 10 5 0 0 5 10 15 Distance (feet) 20 25 30 Figure 84 – 9x9 cloud, 12 in. gap, 14 ft ceiling, cross fire HUGHES ASSOCIATES
© Copyright 2026 Paperzz