Workplace Access Standards

BBC Workplace
Access Standards
BBC WORKPLACE ACCESS
STANDARDS
Ensuring ease of access to BBC buildings for people with disabilities
These access standards will generally apply to all BBC buildings, both freehold
and leasehold.
Standards contained in this document detail the BBC’s commitment to disability
access in line with the Equality Act. Some may go beyond the requirements laid
under British Standards but are deemed desirable by the BBC. Current property
stock and newly leased buildings will endeavor to meet these important
requirements wherever possible. In the case of new property developments
BBC Workplace commits to meeting these standards.
Interpretation of the content of this document as well as more detailed technical
requirements can be provided by the BBC Workplace Disability Risk and
Compliance Manager (ext 01 81654).
Revised: July 2013
1
BBC Workplace
Access Standards
Table of Contents
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
Car Parking
External Approach
Principal Entrance
Reception
Horizontal Circulation
Vertical Circulation
WC Facilities
Evacuating Arrangements
Conference and Meeting Rooms
Refreshment Areas
Studios
2
BBC Workplace
Access Standards
1. Car Parking
How many spaces?
In many BBC buildings the space available for parking is very limited. Where parking exists the
following standards will be adhered to:
 If there are less than 20 parking spaces, at least one of them will be designated and clearly
marked for use by people with disabilities.
 For a car park that has between 21 and 200 spaces, 5% of them (or minimum of two) will be
designated and clearly marked for use by people with disabilities.
 For a car park that has more than 200 spaces, 5% of them will be designated and clearly
marked for use by people with disabilities.
 If the numbers above are inadequate to allow a space to be available for each disabled
motorist, further staff spaces will be converted.
 Where visitor parking is provided, 5% (or minimum of one space) of the total available
spaces will be made available for disabled people.
Where should they be?
 Parking spaces designated for those with disabilities will be as close to the building entrance
as possible and closer to the entrance than any other designated parking bays. This would
normally be within 50 metres if the route is uncovered or between 50 and 100 metres if the
route has a roof. Dropped curbs will be installed where necessary.
The ideal layout
 The layout for car park bays must comply with the requirements laid out in the ‘Design of
buildings and their approaches to meet the needs of disabled people’ BS8300:2009 section 4.
Barriers
 If there is an automatic barrier at the entrance to the car park, it will be easily reached and
operated from a car. If there is an intercom at the barrier it will have a visual indicator for
people with impaired hearing.
 Means of calling for assistance should be provided e.g. a call button located on the barrier
control panel.
 An emergency telephone number must also be displayed at the barrier for the benefit of
people who are deaf or hard of hearing. The phone system at the security control point
should be capable of receiving texts, or a mobile number should also be displayed and
3
BBC Workplace
Access Standards
permanently manned as an alternative method of receiving texted calls for assistance (for
example from people who are deaf or hard of hearing).
 All controls will be located to enable best possible reach. This will normally be between
750mm and 1200mm from ground level.
 Further information can be found in BS.8300:2009 section 4.4.2 and 4.4.3.
Signs
 There will be clear and continuous signage indicating the way to the disabled parking bays and
to the entrance of the building. Signs must be large enough, well positioned to cope with any
change of direction and well lit. Ideally the text and pictogram should be easily distinguished
from 10m away.
2. External Approach
General Approach
The areas outside BBC buildings tend to be busy areas with lots of visitors and traffic - however it
is essential that the means of access are kept clear and free of obstacles.
 Wherever possible the general approach to a building will be uncomplicated and the route
clearly defined and signed.
 Paths adjacent to a building will be kept free of projecting hazards such as open windows,
which might not be seen by people with impaired vision.
 Street furniture such as signposts, litter bins and seats should be located at or beyond the
boundaries of an access route. If such items are present they must contrast visually with the
background against which they will be seen.
 If the path is more than 50m long, seating will be provided for anyone with impaired mobility.
 Further information about access routes, path dimensions and other associated areas can be
found in BS.8300:2009 section 5.
Dropped Curbs
 If the path crosses a road there will be dropped kerbs and blistered paving slabs at each
crossing point.
 The positioning of crossing points/dropped kerbs will avoid gullies and gutters.
Ramps
 If it is necessary to use a ramp to access a building the ramp will comply with standards as
laid down in BS 8300:2009, part 5.8 to 5.10 inclusive, covering the provision of ramps,
landings, lighting and associated hand railing.
4
BBC Workplace
Access Standards
External Steps
 The standards relating to handrails on ramps (see above) also apply when steps are used for
access to a building.
3. Principal Entrance
Entrance to a Building
 The main door to a building will be clearly distinguishable from its façade and if it is glass it
will be clearly visible when closed.
 The door should be well lit and clearly signed.
 Revolving doors will be at least 3 metres in diameter to allow wheelchair users to pass, or
there will be a conventional adjacent powered door that allows unassisted entry to
wheelchair users.
 If there is a double set of entrance doors, they will be far enough apart to allow easy access
for wheelchair users.
 Vision panels will be between 500mm – 1500 mm from the floor to allow wheelchair users
and those with small stature to effectively use them.
 Maximum force required to open a door must be 5 kg (newtons) or less.
 Automatic sliding doors are the preferred option for entrance and reception areas.
 If there is a bell or card reader it will be positioned between 900mm and 1050mm.
 If there is an entry-phone system it should be fitted with a visual indicator to assist people
with impaired hearing. The means of indicating that the call is acknowledged and that the lock
has been released should be both audible and visual.
 A video phone is another option that should be considered when installing or replacing an
entry phone system.
 Further information about building entry covering areas such as access control, door
dimensions, door furniture and clear width requirements are detailed in BS.8300:2009
section 6.0.
Entrance Lobby
 The lighting in the lobby will provide a comfortable transition from the external light level to
that of the reception area. Different light settings may be necessary at night time.
 If there is a barrier mat it will be flush with the floor level (i.e. fitted in a mat-well) and
securely fixed to prevent a possible trip hazard.
5
BBC Workplace
Access Standards
4. Reception
Reception Desk
 Ideally the reception desk will be clearly visible from the entrance door and the route to the
desk will be direct and unobstructed.
 The desk will incorporate a low level area that is accessible for wheelchair users – this will
have a counter that is suitable for writing on and has a least 700mm of clearance underneath.
 The height of the low level counter should be 760mm to accommodate wheelchair users.
 The width of low level counters should not be less than 1500mm
 Any access control system (e.g. barriers or turnstiles) will be easily accessible for wheelchair
users and people with impaired mobility.
 The reception desk will be fitted with a suitably approved induction loop and be
appropriately signed with a pictogram.
 In larger reception areas where multi-positions are in evidence, induction loops could be
spaced sufficiently apart so that there is no overlap in conversion compromising
confidentiality.
 To facilitate lip reading, lighting should be distributed so that both the receptionist and
customer’s faces are evenly lit.
 A portable induction loop will be available from reception for ad hoc use throughout the
building.
 Acoustic requirements must be considered whenever a reception area is designed or
refurbished. Soft fixtures and fittings can often be used to reduce echo and ambient noise
which particularly affects people with impaired hearing.
 There must be an accessible toilet (WC) within 40m horizontal travel of the reception area.
 Further information about reception requirements building entry covering areas such as
access control, door dimensions, door furniture and clear width requirements are detailed in
BS.8300:2009 section 6.0.
Sundry Equipment
Any equipment or facility that is provided within a reception area will be installed keeping in mind
the needs of people with disabilities. The standards below apply to items commonly found in
reception areas; this list is not exhaustive and the BBC will apply the principles of reasonable
access to any other related item.
 Information displays and leaflet racks will be accessible to wheelchair users.
 There will be clear and prominently placed signs showing where key facilities are located –
e.g. accessible toilets, lifts, telephones, etc.
 If telephones are supplied for the use of visitors and the public, at least one of them must be
sited at a height of between 900mm and 1050mm. This phone must also be fitted with
inductive couplers, large push buttons and acoustic side panels. Ideally it should incorporate a
texting facility for people who are deaf.
 If possible there will also be a seat and wall mounted support bar.
 Signs should be in upper and lower case, and tactile if within reach.
6
BBC Workplace
Access Standards
 Ideally there should be printed or tactile maps available or an explanatory model of the
building to provide directional information.
 Any vending machines should be fitted with controls that are no higher than 1050mm and
easily accessible dispensing drawers.
Seating Areas




Chairs will have firm backs and arms to aid people with arthritis or back complaints.
Tables will be at a height that is accessible to wheelchair users.
Space will be made in seating area layouts to accommodate wheelchair users.
Colour schemes will be chosen to ensure that furniture is easily distinguished from its
surroundings.
General
 The floor surface will be slip resistant, even when wet.
 The acoustics of a reception area will be considered when choosing floor coverings and
furniture. Echoes often cause problems for people with impaired hearing.
5. Horizontal Circulation
Corridors
 Corridors will have a minimum clear width of 1200mm (preferably 1800mm) to ensure
access for wheelchair users.
 Corridors will be step free wherever possible or be fitted with ramps.
 Floor patterning that could be mistaken for steps, e.g. stripes, should not be used for floors
in corridors.
 Appliances and fittings will be positioned in such a way that they do not present a hazard to
wheelchair users or people with impaired vision.
 Office doors will not open into the corridor (although disabled toilet doors may need to do
so).
 Wall-coverings that minimise reflected light and sound reverberation will be used.
 Directional signage will be distinct and consistent along all routes, prominently placed and at
a reasonable height for wheelchair users.
 The décor in corridors should be designed to provide high contrast between doors, walls
and floors – monochrome colour schemes should be avoided.
Internal Doors
 All doors will be in a colour that is distinctly different from the wall to make them easily
distinguishable for people who have impaired vision or colour blindness.
7
BBC Workplace
Access Standards
 Door handles must be of the lever or pull variety (i.e. not knob). They will be easy to grip,
not more than 1000mm high and have at least 300mm of clear space around them.
 Door handles will be of a contrasting colour to the door.
 Vision panels will be between 500 and 1500mm from the floor to allow wheelchair users to
use them.
 Door closers will be set to the minimum necessary force – no more than 5kg – and should
have a slow action.
 All circulation doors should ideally be fitted with 400mm kick plates.
 Fully glazed doors and any associated screening will incorporate suitable manifestation as
described in BS6262 Codes of practice for Glazing of Buildings.
 Some internal doors may benefit from automation or magnetic hold back for a range of
reasons. Such installations first need to be agreed with the Workplace Disability Risk and
Compliance Manager who will be able to provide best practice advice.
 Further guidance about this topic can be found in BS.8300:2009 section 6.4.1 to 6.6.4.
6. Vertical Circulation
Lifts
 Lift lobbies will have at least 1500m x 1500m of unobstructed floor space.
 Lift doors will have at least 800mm of clear width but at least 900mm for buildings used by
the general public.
 Lift cars will be at least 1100mm wide x 1400mm deep.
 If there is not enough room within a lift car to allow a wheelchair to turn around, it will be
fitted with a mirror on the rear wall.
 Lift cars will be fitted with a handrail on all walls, 900mm high and at least 45mm clear of the
wall.
 Internal and external lift controls will be between 900mm and 1200mm high and fitted with
tactile buttons.
 If a lift serves more than three floors it will be fitted with both visual and audio indicators.
 All lifts will be fitted with an operational re-opening activator.
 The alarm buttons and emergency handsets should be fitted with visual
indicators.
 If a lift car is particularly wide (3.5m) there should be controls fitted to both sides.
 There should be a clear sign on each landing showing the floor or level.
 If there is an emergency telephone it should be fitted with an inductive
coupler and whenever possible it should incorporate a texting facility for deaf people.
 Further information about the provision of lift equipment can be found in EN81 part 7.0. and
BS8300 part 8.3.
Platform Lifts
 A platform lift may be installed in place of a ramp.
8
BBC Workplace
Access Standards
 Platform lifts must allow self operation and be fitted with a landing barrier arm.
 Platform lifts must be able to cope with weights of at least 225kg to include battery operated
wheelchairs.
Evacuation Standard Lifts
 There will be at least 1000mm clearance between handrails.
 Where possible evacuation standard lifts should be provided as this makes the process of
evacuating the site much easier, particularly for wheelchair users.
 These lifts will normally be found in larger high population sites.
Internal Stairs
 There will be at least 1000mm clearance between handrails.
 The handrails on staircases will be continuous on both sides of the staircase (1000mm high
on landings and 900mm on the staircase). With a handrail overrun of 300mm at top and
bottom.
 Handrails will be easily distinguishable from the wall to which they are fixed.
 Nosings will be easily distinguishable from the rest of the step (see ‘External Steps’ section
2).
 There should be tactile indicators at the top and bottom of all staircases as well as visual and
tactile floor indicators. This does not apply to mid-flight landings unless there is a door
leading from them.
 Further information about this area can be found in BS.8300:2009 section 5.9 and 5.9.2 and
section 8.0. Also BS.5395.1:2000.
7. WC Facilities
Location and Number
 There will be a disabled toilet facility within one floors’ travel from anywhere within the
building, and no more than 40 metres horizontal travel from any given work area.
Dimensions
 A disabled toilet facility will be no less than 2000mm x 1500mm (if it is laid out in a
‘peninsular’ arrangement it will be at least 2500mm(w) x 2000 mm(l).
9
BBC Workplace
Access Standards
WC Doors
 The doors to toilets for wheelchair users will allow at least 860mm clear opening (1000mm
doorset).
 If the toilet is designed to the minimum allowable dimensions the door will open outwards.
 The latch or lock must be easily opened from the outside, but must not interfere with the
occupant’s privacy.
 The latch or lock will be easily opened by people with impaired manual mobility (the throw
over latch system is best).
Washing Facilities
 The hand-basin and drier or towel (preferred option) must be accessible from the WC.
Transfer Space
 There will be a minimum of 750mm unobstructed space to one side of the WC (this will be
alternated from side to side for WCs on different floors.)
WC Seat Height
 The top of the seat will be 450mm high.
Grab Rails / Support Bars
 There will be a hinged rail fixed to the wall on the open side of the WC.
 There will be a fixed rail on the wall on the closed side of the WC.
 The rails will be securely fixed, warm to the touch and finished in a colour that contrasts
with the wall.
Emergency Alarm
 There will be a pull cord, in a distinctive colour, reaching close to the floor that can be easily
pulled in the case of an emergency; however it is important to check that it will not be easily
activated by accident.
 The alarm will be clearly visible and audible, and positioned where it will always generate a
prompt response.
 The provision of a second alarm may be required in very large or unconventionally shaped
toilets.
Décor
 The use of shiny wall and floor coverings will be avoided.
10
BBC Workplace
Access Standards
Hoists and Changing Beds
 A few people with specific or sometimes severe disabilities may need to use a toilet hoist and
this might need to be accompanied with a specialised changing table. Such equipment (at least
a hoist) should be routinely available in all major BBC sites.
 The hoist may be permanently installed or could be portable.
 In respect of newly built major sites it is important to ensure that one or two larger than
normal disabled toilet areas are provided to allow such equipment to be installed.
8. Evacuation Arrangements
Equipment
Some disabled people may require assistance in evacuating a building, particularly from upper or
lower floors. This might be as simple as accompanying a disabled person to leave site via a
standard fire route. The evacuation process could however involve the use of a specially
converted lift or other equipment to traverse stairs. Methods of evacuation and some of the
equipment involved may include the following:
 Through the use of a suitably converted fire protected evacuation lift (best practice) - see
section 6.
 Through the use of a motorised evacuation chair.
 By using a portable non-mechanical evacuation chair (most used method).
 Through horizontal evacuation routes (sometimes used in larger sites).
On some sites a combination of the above methods are often used.
All BBC staff requiring assistance with evacuation must have a current personal emergency
evacuation plan (PEEP) in place.
For disabled visitors requiring assistance with evacuation the visitors host must ensure that a
visitor PEEP is completed. This will need to describe the specific evacuation arrangements that
have been set up.
For further information on PEEPs, refer to the ‘My Risks’ website via Gateway.
11
BBC Workplace
Access Standards
9. Conference and Meeting
Rooms
Signage
 Conference and meeting rooms need to be clearly sign-posted from all key areas within the
building.
Access
 The circulation routes within meeting rooms will kept clear of obstructions and allow at least
900mm clearance for wheelchair access.
Furniture
 Tables will allow clearance for wheelchairs users (approximately 650mm – 700mm high).
 There should be some free-standing chairs, with arms, and a minimum height of 475mm.
Communication
 Portable induction loops will be made available for use in meeting rooms but these are
normally limited for 1.1 conversations such as interviews etc. In larger meeting rooms and
particularly in principal sites a fixed induction loop system may be also be installed.
10. Refreshment Areas
Access
 A minimum of 20% of the seating area will be made accessible for wheelchair users. This
includes all the service options available to other customers (e.g. self-service and table
service – smoking and non-smoking areas etc.).
 The circulation routes to refreshment areas will be free of obstructions and allow at least
900mm clearance for wheelchair access.
12
BBC Workplace
Access Standards
Self-Service Arrangements
 Queuing or service aisles will be no less than 900mm wide with a continuous counter tray no
more than 900mm high.
 Food shelves and drinks dispensers will be no greater than 1350mm high and within 500mm
reach from the edge of the counter.
 If possible a support will be provided.
 Menu displays will appear in a clear large print format (preferably Gill Sans or Ariel, minimum
16pt).
Pay Points
 The aisle space at pay points will be at least 900mm wide.
 At least part of the counter will be less than 800mm high to enable wheelchair users to write
cheques.
Furniture
 There will be some tables with clear knee space for wheelchair users (700 – 750 mm).
 There will be some removable seating to allow space for wheelchairs, or where seating is
fixed, suitable space for wheelchairs.
 There will be some free-standing chairs, with arms, and a minimum height of 475mm (suitable
for people with guide dogs).
 There will be an accessible WC within 40 metres of a restaurant.
 The accessible WC will be clearly signposted from within the restaurant.
11. Studios
Audience Assembly / Holding Area
 It is often necessary for security reasons to hold an audience before allowing them into the
studio. This room or area will be fully accessible for wheelchair users and be equipped with
appropriate seating for people with impaired mobility.
 It is also important for the room to be served by an infrared hearing system.
Green Room or Assembly Room for Contributors
 This room or area will be fully accessible for wheelchair users and be equipped with
appropriate seating for people with impaired mobility.
13
BBC Workplace
Access Standards
Studios and Sound Lobbies
 These areas will conform to the dimensional requirements of Part M of the Building
Regulations; i.e. minimum space of 1200mm square.
Control Galleries / Cubicles
 These areas will be accessible to wheelchair users.
Circulation Routes within studios
 Safe walkways and circulation routes will have a clear unobstructed width of 900mm.
 These areas will be kept free of props and scenery, and cables will be suitably ramped or
‘flown’.
Seating positions for wheelchair users
 If there are less than 20 audience seats available; at least one of them will be fully accessible
for a wheelchair user.
 If there are more than 20, but less than 200 seats available; 5% of them or two (whichever is
greater) will be fully accessible for wheelchair users.
 If there are more than 200 seats available, 2% of them or six (whichever is greater) will be
fully accessible for wheelchair users.
 Wheelchair seating positions will have a clear space of at least 900mm wide by 1400mm
deep.
 Wheelchair seating positions will be available in a variety of positions (e.g. front and back of
studio).
 For larger studios wheelchair users will be given the opportunity of sitting next to each other
if desired.
 Suitable seating for ambulant disabled people: some easy access seats will be made available
either at studio floor level, or with a handrail if the seating is stepped. These seats will have a
clear leg space or seating aisle width of at least 650mm.
 Seating will be made available with sufficient adjacent space for a guide dog to lie down.
 Some loose seating with appropriate back and armrests should be made available.
Permanent stages and podia
 If a raised stage or podium is a permanent fixture of a studio, it will be accessible by suitable
ramp (i.e. with handrails and a gradient of less than 1:12 or platform lift.
 An adjustable lectern should be made available for wheelchair users or people of small
stature.
Accessible dressing rooms
 If 10 or less dressing rooms are required for a production, at least one of them will be made
accessible for wheelchair users, and be situated not more than 40m from the studio.
14
BBC Workplace
Access Standards
 If more than 10 dressing rooms are required, two of them will be made accessible to
wheelchair users and situated not more than 40m from the studio.
 Accessible dressing rooms will have an integral WC whenever possible.
Communication Aids
 Studios and accessible dressing rooms will normally be fitted with an infrared
system.
hearing
------------------------------------------------------------------------------------
15